How safety is demonstrated
Regulations and filter integrity
Filters must not only work – they must be demonstrably shown to work correctly. For use in aseptic manufacturing, what matters is therefore not just a filter’s performance but also the documented evidence of that performance.
Relevant standards:
ISO 14644-1 (cleanroom classification)
ISO 14644-3 (test methods)
ISO 29463/EN 1822 (filter classification and testing)
EU GMP Annex 1 (requirements for aseptic processes)
A distinction must be made between two levels of testing: filter class and leak-tightness are verified by the manufacturer on a test rig. Once the filter is installed, the question is whether this condition has been maintained Has the filter remained undamaged during transport and installation?
Two methods are available for on-site integrity testing: the overall leak test, which assesses the overall performance of the installed filter, and scanning, which detects local leaks in the filter medium. A filter can meet overall performance requirements and still have local leaks. Scanning is therefore used for terminal filters located directly above the product.